EOCR Thermal Overload Protection Relay

EOCR Thermal Overload Protection Relay
Product Detailed
Related Categories:Relays
1.International Standard: IEC 60947-4-1 2.high qulaity with low price. 3.Ampere have different range from 5A, 10A---80A.

1.Feature:

EOCR-SS electronic overload relay is suitable for AC 50/60Hz, voltage up to 600VAC and currentup to 60A. It is used as overload and phase loss protection, independently adjustable startingand trip delay, visual current setting aid and trip indication, fail safe protection (N type) andelectronic shear pin function. The product conforms to IEC60947-1 standard.

2.Specification and Technical:

Type

EOCR-SS

Current range

05)0.5-5A(scale 6.5A)

30)3-30A(scale 35A)

60)5-60A(scale 70A)

Rated voltage

600VAC,50/60Hz

Operating setting

D-TIME

0.2-30 seconds

O-TIME

0.2-10 seconds

Accuracy

Current

±10%

 

Time

±15% of max.time set value

Time characteristics

Definite time

Control voltage

220)Voltage free(90-260)VAC,50/60Hz

440)Voltage free(320-480)VAC,50/60Hz

Other voltage optional.

Current sensing

2 CTs

Output contacts

Contacts

SPDT 3A/250AVC Resistive

Contacts

N  Type

Normally energized:9598closed

R  Type

Normally De-energized:95  98closed

Reset

Manual or remote electrical by interrupting supply

Environment

Temp.Run

Run

-20+70 deg.oC

Store

-30+80 deg.oC

Humidity

45-85% RH,non-condsing

Insulation

Between casing and circuits:Over 10MΩwith DC 500V megger

Dielectric strength

1)Btween casing and circuits:AC 2000V,60Hz,1min

2)Btween contacts: AC 1000V,60Hz,1min

3)Between circuits:AC 2000V,60Hz.1min

Power consumption

Under 2W

Mounting

35mm Din Rail(D)

3.Package ready for shipment

4.Package ready for shipment

5.Production Line:

6.Certificate List